Multi-line 2 GC-1F Application Software series 2.x.

You’re about to download Multi-line 2 GC-1F Application Software series 2.x.

The software you are trying to download is obsolete. Please download the latest version from this page.

You have chosen to download our software.

Within a few seconds, you will receive an email containing a download link.

Having trouble using the software? Please contact support@deif.com. 

Best regards, 

DEIF A/S

The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software

This software applies to the following DEIF products:

You’re about to download 2.33.0

The main changes implemented since the last version are as follows:

New features:

  • Five M-Logic alarms have been added.
  • In the AMF variant the inhibits "Genset Hz/V NOT OK" and "Mains Hz/V NOT OK" have been introduced. In the ATS variant the inhibits "Source 1 Hz/V NOT OK" and "Source 2 Hz/V NOT OK" have been introduced.

Changes:

  • Timers have been removed from #2240 and #2250. The alarms are now instant.
  • Sleep mode can no longer be disabled.
  • The sleep mode timer will now start running even though an unacknowledged alarm is present. Furthermore the alarm LED is no longer turned off when sleep mode is active.

Corrections:

  • While an ATS was powered down and a source went bad, the ATS would not go to a healthy source when it powered back up in auto. This correction only affects ATS controllers with pulse breakers.
  • The controller no longer tries to reclose the breaker when an active alarm is configured with Trip MB or Trip GB fail classes.
  • The ATS now considers a breaker, tripped by a fail class, the same as a mains failure, and will change source if healthy.
  • Extended stop timer is now activated if running feedback disappears abruptly.

 

Ver. Date Description

2.33.0

16/03/2017

New features:

  • Five M-Logic alarms have been added.
  • In the AMF variant the inhibits "Genset Hz/V NOT OK" and "Mains Hz/V NOT OK" have been introduced. In the ATS variant the inhibits "Source 1 Hz/V NOT OK" and "Source 2 Hz/V NOT OK" have been introduced.

Changes:

  • Timers have been removed from #2240 and #2250. The alarms are now instant.
  • Sleep mode can no longer be disabled.
  • The sleep mode timer will now start running even though an unacknowledged alarm is present. Furthermore the alarm LED is no longer turned off when sleep mode is active.

Corrections:

  • While an ATS was powered down and a source went bad, the ATS would not go to a healthy source when it powered back up in auto. This correction only affects ATS controllers with pulse breakers.
  • The controller no longer tries to reclose the breaker when an active alarm is configured with Trip MB or Trip GB fail classes.
  • The ATS now considers a breaker, tripped by a fail class, the same as a mains failure, and will change source if healthy.
  • Extended stop timer is now activated if running feedback disappears abruptly.

 

2.32.0

16/09/2016

New features:

  • Parameter #2240 and #2250 external trip alarm of GB/CB1 and MB/CB2 has been added.

Changes:

  • Sleep mode is now enabled by default. If any alarms are present, they have to be acknowledged for the display to turn off the backlight.

Corrections:

  • Breaker open feedback alarms removed two seconds when breaker open signal is given and the alarm is already acknowledged.
  • It is now possible to reset an external IO setup from the display of the GC-1F.
  • An ATS unit will no longer automatically open its breakers when in manual mode.
  • A GC-1F ATS configured with pulse breakers could issue an open pulse when powercycled. If pulse breakers and breaker feedback is configured, it will now maintain the breaker positions from before the power cycle.
     

2.31.1

19/12/2014

  • Support for HW revision 7 added.

2.31.0

02/10/2013

New features:

  • Added EIC support for priority 7 on diagnostic message 1 and 2.

Corrections:

  • Minimised the risk of communication error on the service port.
  • EIC coolant temp., oil temp. and charge air temp. scaling are corrected for MDEC 302 and MDEC 303 protocols. 
  • Incorrect M-Logic interpretation corrected.
  • EIC transmission rate of CAN telegrams is corrected for the Volvo Penta protocol.
  •  Day of week is automatically adjusted when the date is changed.

2.30.0

29/06/2012

  • Support of upcoming hardware (1.06) implemented.
  • EIC: MTU Smart Connect 'EIC faults' handled correct.
  • EIC: EIC idle speed also set if a digital input is configured as IdleSpeed and input is activated.

2.24.0

12/03/2012

  • Supply voltage showed correct if large changes (above 10V) occurres.
  • Relay 3 available as limit relay.
  • EIC: Receiving single DM1 diagnostic not restricted in content any longer for all J1939 protocols.
  • EIC: Occurrence counter available in DM1 and DM2 logs.
  • EIC: Scania EMS speed offset handling corrected.

2.22.0

19/05/2011

  • Breaker pulse feedback handling improved for handling flicker.
  • Selection of language from USW saved correctly in unit

2.23.0

12/05/2011

New features:

  • EIC: MTU J1939 Smart Connect supported (see documentation).
  • EIC: After treatment / Diesel Particular Filtering implemented.
  • EIC: Caterpillar (Perkins): Two DM1 logs available for support of ADEM (primary) and EMCP (secondary) at the same time.
  • EIC: Caterpillar (Perkins): Start/stop signal to ECU can be enabled/disabled via M-logic.
  • EIC: Speed control signal to ECU can be inhibited (enabled/disabled) via M-logic.
  • EIC: Inhibit of EIC alarms can be setup via M-logic.
  • EIC: Standard GC-1F/2 Idlerun functionality now turns the engine to 700rpm on different engines (see documentation).
  • EIC: Protection lamp status and Malfunction lamp status implemented on J1939.
  • EIC: Both priority 3 and 6 are supported for Dash Display PGN, DM1 and DM2 logs.
  • EIC: Cummins: Shutdown override signal available.
  • EIC: Coolant level alarms (2 levels) implemented in menu 7670+7680.

Changes:

  • EIC: Support of 19bit SPN numbers in DM1 and DM2 logs.
  • EIC: Engine hours available available up to 99000hours in display readout.
  • EIC: When changing nominal frequency, a ramp function will be performed.
  • EIC: Modbus readings of a few EIC data; Coolant temperature, Fuel temperature and Charge Air Temperature where presented with different number of decimals depending on the engine protocol selected. This has now been aligned so data is presented in the same manner independent of engine protocol selected.

Corrections:

  • External I/O: Recognition of modules during power up secured for general I/O variants e.g. Wago. Correct recognition could randomly fail.
  • External I/O: Actual number of digital inputs are handled correct for general I/O variants to prevent wrong status indications in USW Input/output window.

2.21.0

25/03/2011

  • Shutdown override inhibit flag respected, so only alarms with failclass shutdown and no inhibit, stops the engine during a shutdown override period.
  • Reset of fire pump (shutdown override) hour counter possible from USW.
  • Engine Interface Communication: Transmit rate of speed telegrams (FF46 and TSC1) to VolvoPenta EMS2 increased from 40ms interval to 20ms interval.
  • Engine Interface Communication: Speed ramp increase and decrease setting increased to ±1500rpm and nominal rpm setting is used as start up point.
  • Setup of Number of teeth available from the device.
  • Setup of Language available from the device.
  • Setup of CT secondary available from the device.
  • Setup of CT primary available from the device.

2.00.0

01/03/2011

Initial release

  • Compared with version 1.23.x you get:
  • Status OK relay on terminal 3-4 is now configurable.
  • Able to work down to -40°C via option L2. Option L2 is a display heater hardware.
  • Short circuit protection up to 350% current.
  • All three VDO’s have a 0-2500ohm range.
  • Backlight dimmer control via display or USW.
  • Auto Acknowledge on selected alarms.
  • Power up added to event log.
  • LED indication during download of firmware.

Extra's

  • Parameter files from version 1.2x.x can be reused in the 2.xx.x software.

2.20.0

28/02/2011

  • ATS mode implemented (generator-mains and source-source).
  • Various ATS switches supported (2COMH, 2COEH, 3COMH, 3COEC etc).
  • Remote breaker handling implemented.
  • Remote mode change implemented.
  • Parameter for startup mode implemented.
  • Auto-mode shift parameter implemented.
  • Generator / mains OK inputs implemented for ATS mode.
  • Bypass to generator / mains inputs implemented for ATS mode.
  • Mains ok / fail status outputs implemented.
  • Source 1 and source 2 start /stop outputs implemented for ATS mode.
  • Testmode indication in display.
  • Testmode timer adjustable from display.
  • Breaker status outputs implemented.
  • Operation mode outputs implemented.
  • Busbar over/under voltage protections implemented (2 levels).
  • Busbar over/under frequency protections implemented (2 levels).
  • Inhibit functionality added to several parameters.
  • Handling of setup with no breakers improved.
  • Idle mode via digital input improved for AUTO mode.
  • Phase sequence protection improved for pulse relays

2.00.1

03/01/2011

  • Multi inputs in mA (or configured unit) display range increased from ±10000 to ±32000
  • Cut off level for AC measurements improved.

2.10.0

03/01/2011

  • Off mode implemented. The gen-set is completely blocked when entered OFF mode.
  • Engine Interface Communication: Speed ramp increase and decrease via digital inputs implemented.
  • GB and MB pulse control implemented.
  • Q> (Q export) and -Q> (Q import) protections added.
  • Option M19 added. Relay 47 is normally closed in standard hardware, but normally open if option M19 is chosen.
  • Support of general External IO modules following CiA 401. This is the CANopen device profile for generic I/O modules. Beckhoff, WAGO, Schneider, and many other brands use this protocol and now supported by GC-1F.
  • Support of 11 languages.
  • Log: New entries in event log for test sequence start.
  • Inhibit functionality added to several parameters.
  • Enable/disable functionality added to several parameters.
  • VDO fuel user defined curve display readout range changed to follow the two most extreme points.
  • Extended timer range for Stop failure alarm.
  • Engine Interface Communication: New measurements available ADEC protocol.
  • GSM: Channel number added and Header info removed from SMS message send when alarms occurs.
  • Engine Interface Communication: Improved support of preheat for Volvo Penta EMS 2.
  • Engine Interface Communication: Improved support of IVECO engine status.
  • Handling of kWh counter reset improved: Unwanted reset during power cycle prevented.

On this page, you can download software updates for your product(s) and help yourself to various utility tools and add-ons that will assist you in setting up, detecting faults and configuring your product(s).

Please be advised that not all of our products can be updated by the user. Nor do all of our products come with a utility tool. Consequently, the list on this page cannot be considered an overview of our product programme.

DEIF will register your download along with the used e-mail address for the purpose of sending out information on future updates, if requested.

DEIF cannot be made responsible for any consequences of failed product updates or use of utility tools. Nor can DEIF A/S be made responsible for consequences of changes in behaviour of products due to a software upgrade. It is always the responsibility of the user to ensure correct set-up and configuration before commissioning. Please study the version log of the software before updating the product.

Licence agreement for software downloaded from www.deif.com

Downloaded software remains the property of DEIF. The software may not be distributed for commercial purposes, changed or reused in full or in part or sold to any third parties.

The latest versions for full functionality

As always, we recommend that you install our offered improvements to fully utilise your DEIF product.

All improved software can be downloaded at your convenience at www.deif.com under “Software”.

Should you have any questions or experience problems finding the relevant software for your product, please feel free to call DEIF A/S at +45 96149614 or your relevant local DEIF office. Alternatively, we are always ready to assist you, if you send an e-mail to support@deif.com.