3.12.5 | 04/01/2023 | Corrections: - SWBD CONTROL for status text and event log made translateable.
- Start+Sync can now tolerate a dip below OK level on the busbar.
|
3.12.4 | 10/03/2022 | Corrections: - Running hours shown correct on GPU/PPU-2 Modbus RS-485 / ProfiBus interface.
|
3.12.3 | 27/08/2021 | Corrections: - View text for DU-2 available for translation.
|
3.12.2 | 05/08/2019 | Version 3.12.2 based on 3.12.1 Corrections: - Modbus addresses for relay status on EF5-option not active.
- PPU-2 protocol converter in PPU-3 not working for Profibus.
|
3.12.1 | 10/09/2018 | Corrections: - Log value disappears after power cycle on display.
- Log did not appear in USW before the unit had been power- cycled.
- Option M15.8MKII Delta alarms were not available on display.
|
3.12.0 | 08/01/2018 | New features: - Added menu 2800 where it is possible to disable power ramp functionality in fixed power regulator.
Changes: - Axiomatic PGN 0xFEA7 source address has been changed into A0.
Corrections: - External I/O views will no longer toggle to zero at display.
- Improved update of TCP/IP Modbus data. TCP/IP Modbus is no longer slow when no display is connected to unit
- MTU MDEC 2000/4000 M.302 and MDEC 2000/4000 M.303: False EIC alarms can under rare conditions occur. (option H5)
|
3.11.0 | 15/03/2017 | New features: - Add M-Logic signal: Waiting on spring loading
- Added PGN FEA7 byte 0 and 1 to axiomatic
- Added alarm for break open df (parameter 2623) and increased range to 10.0 Hz
Corrections: - Added possibility to change TSC1 source address for J1939 protocols.
- EIC measure alarms inhibit during EIC communication fail.
- Frozen reading input on external I/O module.
- The slip-frequency comparison to sync parameters improved. Ensures that two equal frequencies can be synchronised together.
- kWh day, week, month could not reset if it was powered down when passing 00:00.
- The state of relay 69 and 71 when using option EF4 will now be detected correctly.
- Ext. Comm. Protocol Version (parameter 7514) was not available on H3.
- Ext. Comm. Protocol Version (parameter 7514) submenu text corrected to GPU/PPU-2.
- When using GPU/PPU-2 Modbus, only 78 addresses could be read.
- Modbus address 1068/1069/1070 duplicated to 1056/1057/1058.
- When using GPU/PPU-2 Comm. Modbus, the voltage could not be read.
- A position failure alarm could also trigger a close failure alarm.
- Hz/V OK (parameter 6221) timer corrected to 0 sec.
|
3.10.0 | 25/08/2016 | New features: - Added view lines for BTB A – D positions.
- Added memory backup function.
- Added genset not asynchronous alarm.
- Added menu for TCP/IP settings 7900, 7910 and 7920.
- Added software download via TCP/IP (bootloader version 1.03.0 or newer required).
- Added troubleshooting CAN bus connection on jump menu 9250.
- Added permissions possibility in USW.
- Added clear log possibility in USW.
- Added parameter-edited flag possibility in USW.
- Added possibility to change between BB nominal settings 1 or 2.
- Added ramp speed 2.
- Added auto ramp speed selection.
- Added droop active M-Logic events
- Added ramp speed activation M-Logic commands.
- Added Option H13: MTU ADEC Module 501.
- Updated to latest engine protocol/module incl. MTU Smart connect.
- Expanded delta analogue input list to include exhaust temp. left/right.
- Added support of Axiomatic interface (M4 Prot. version 1.01.0 or newer required)
- Added CAN line selection at menu 7840
- Added view for external set point.
- Regulator LED will turn yellow if regulation output is not set.
- Expanded delta analogue input list to include EIC T. Exhaust.
- Added BTB deload.
- Added frequency detection parameter for running detection.
- Added easy change between Metric/US units at menu 6920.
- Added “CAN1 comm error” and “CAN2 comm error” to M-Logic.
- Added Inhibit of MTU shutdown override
- Added MTU speed demand switches.
- Added VOLT/FREQ NOT OK info text.
- Added PPU-2 Modbus Compatibility Mode via menu 7514 (Option H2)
Changes: - Removed menu 2280 and 2290 from PPU-3.
- Removed ethernet fail menu.
- Increased event log size to 500.
- Increased alarm log size to 500.
- Increased virtual event on M-logic to 42.
- Increased TCP/IP refresh rate.
- Changed shutdown override to be a part of inhibit.
- Improved precision of analogue inputs to be within class 1.0.
- All P/Q/cos phi droop types will now use the present value at droop start as reference point of the droop.
- Power droop slopes are now scaled based on the droop start reference point as a percentage of the nominal power.
- Q-droop limits are now ranging from -20000 to 20000.
- Scaling range has been changed from 1 kV–75 kV into 0.4 kV–75 kV
- Changed status text MANUAL to NO REGULATION if start sync/ctrl is not set and a GOV/AVR mode is selected.
- Frequency set point from Modbus or analogue input accepted regardless of the GB state.
- Support of ADEC CANopen, shutdown override.
- When M-Logic cool down threshold is selected, it will be used although the parameter is 0
- Cool down threshold will be ignored if used together with a multi-input and it has wire fail.
Corrections: - Strange characters in text could appear when read from Option N.
- M-Logic could be evaluated wrongly.
- Adjustment of clock from display did not work.
- Service timer days did not adjust when date was set from display.
- Moved digital inputs on Modbus.
- Updated M-Logic alarm list with "Ext. comm error".
- Single phase PF measurement could show a PF higher than 1.00
- S L1, S L2 and S L3 did not update on Modbus.
- Mains sync inhibit protections was inaccurate.
- Asynchronous generator stop did not work.
- EI Comm. error was constantly activated for the Caterpillar protocol.
- Vector mismatch did not work with single and split-phase measurements when sync. time was longer than the timer set point of the alarm.
- M4 with H7 could have an abnormal update on the CAN bus.
- VDO renamed to RMI.
- Wrong DM1 alarm could appear on the display.
- External I/O: Analogue input scaling and unit were configured incorrectly at start-up and when engineering unit was changed.
- Menu 9000 handling did not work properly.
- Scania start/stop did not work on H7.
- M4 multi-input went high when nothing was connected.
- Battery voltage on MDEC 302/303 protocols was a factor 0.1 wrong.
- Alarm “AL Speed Demand Failure” was always present when connected to MTU 1600 series engines with a SMART CONNECT module.
- CAN-line faults could make the display very slow.
- Positive/negative/zero sequence was not able to handle short circuit and open conductors on all phases.
- Change of engine communication protocol could cause the texts in a parameter file to get corrupt.
- The scaling in frequency-dependent power droop and power offsets was wrong.
- The text for CAN id missing referred to CAN2 when CAN1 was used.
- Change of voltage scaling did not update in USW when Option N was used.
- GOV and AVR mode undef. Modbus alarm bits did not update when alarm was present.
- A unit alone on an analogue load share line with P load share select with ramp up enabled could ramp up to random value.
- When an offset for running hours was added, it was not shown correctly on the display.
- Reinitialise of CAN on single CAN card could cause the communication to stop.
- Idle run could cause external start not to work.
- Change of multi-input decimals or unit could cause a wrong display value.
- EIC alarms used as a low alarms would appear when the CAN communication was lost.
- The unit could get stuck ramp-up mod and never reaching its ramp up set point.
- Update for analogue load share line was only done once in each scan.
- Scaling menu 12000 for Beckhoff 3022 module was lost after power off.
- CAN line could not restore after a short circuit
|
3.10.1 | 25/08/2016 | This software applies to the following DEIF products: - Multi-line 2 - PPU v.3.xx Marine
- Multi-line 2 - GPU v.3.xx Marine
Changes: - Parameter configuration attributes: Auto acknowledge is never set to "ON" by default
- "Clear log" no longer possible from USW
|
3.09.7 | 07/10/2015 | Corrections: - SMS/E-mail alarm functionality corrected (Option N).
- “Remote start and close GB" and "Remote open GB and stop" functionalities have been corrected.
- Different alarm fail classes can now be selected for analogue input 95 (menu 4060).
- Stop-coil wire break alarm can now be enabled through USW.
- Corrected support to MTU engine (SAM module) via J1939 protocol.
- Update of energy reading and correction of display reading in regard to different scaling settings.
|
3.09.6 | 21/03/2015 | Corrections: - Update of self-check functionality
- Idle run were missing in emulation
- Idle run activation through digital input and reactivation after stop button functions have been corrected.
|
3.09.5 | 01/12/2014 | Corrections: - No alarm was displayed when horn, siren or common alarm were combined.
- Hz/V ok is lost during synchronisation, the synchronisation is aborted regardless of fault class.
- After flashing new application software, the unit started up in Remote. This is changed to Local.
- Stop coil did not activate when start sequence was aborted.
|
3.09.4 | 15/10/2014 | Corrections: - "Wrong password" is displayed in secondary display at a correct password.
- RPM control (for asynchronous generator) using relay outputs; parameter set by user not utilised.
- TCP/IP Modbus reading of enable bit incorrect.
- TCP/IP Modbus control registers not updated.
- Theoretically, AVR reactive power regulator can be wrong.
- Q can be forced into overflow in Q(P) protection.
- Start enable has to be energised to activate the regulation.
- Inverse over-current protection modified to better comply with IEC 60255 Part 151. For further information, see the designer's reference handbook.
- Parameter 1083 TMS inverse over-current, TMS changed from 1/10 to 1/100.
- BTB position is not communicated over the CAN line. Alarm added if only one feedback is used.
- BTB position fail parameter numbers differ from parameter list and H2 manual.
- Navigation in menu 9140 is incorrect.
- Wrong Modbus alarm on M15.
- Phase/neutral and phase/phase measuring mixed up when used for detection.
- P-loadshare EXT with CANshare cannot be enabled from M-Logic.
- SWBD mode did not work with option M4.
- TCP/IP could cause the unit to reboot.
- Power ramp-up set point calculation was incorrect.
- Virtual event 1-16 missing on Modbus address 62 and virtual event 17-32 on address 63.
- Reset of H8 analogue input parameters at power-up of unit.
- Inhibit of Modbus command through M-Logic was not working.
- The reactive power is wrong when the phase rotation is L1L3L2.
- Issue when requesting "Remote GB OFF + stop" right after a "Remote start + GB ON" command.
- Parameters 1201 + 1202 should not be present if 3-phase is configured.
- EIC protocol change could cause the unit to reboot.
- EIC Exhaust temperature left/right is missing in menu 460x and 467x.
- Automatic update of jump menu-related parameters when reading through TCP/IP.
- Multi-input in binary mode is now represented on I/O page in USW when reading through TCP/IP.
- Now stopping GOV/AVR relays from regulating after the GB is closed
|
3.09.2 | 22/10/2013 | - Initial release of special Marine approved ML-2 SW
|